Auxiliary power supply for use with thepcpr or dcpr or irc-3 modules. Upon loss of primary power or brownout condition, power supply is transferred to secondary or battery power. Internal battery charger capable of charging 60 ah batteries; voltage: 120 vac 50/60 hz; current: 2 amp; battery charger voltage: 26.8 vdc; charge current: 4.0 amps; trickle charge: 10 ma out 1 and 2: 3.5 amps; amplifier power: 3.5 amps; standy current 2.25 amps; alarm current: 7.5 amps; high sense: 47 k ohms; low sense: 10 k ohms; temperature range: 32 to 120 degree f (0 to 49 degree c); 85 percent humidity, non condensing; mounting: full frooprint module