2 electrically isolated coils; coil number 1 time delay; coil number 2 instantaneously tripped by curren (220.0 volts, 50.0 to 60.0 hertz, 30.0 va) , supplied by control equipment or remote monitoring system; ultimate trip rating for coil 2 is 120.0 percent
MRC:
The style designation indicating the configuration that most nearly corresponds to the appearance of the body.AAQL
Body Style:
Multipole-single actuator type
MRC:
A measurement taken at right angles to the length of the mounting slot,in distinction from thickness.ABTD
Mounting Slot Width:
0.203 inches
MRC:
A measurement of the longest dimension of the body,in distinction from width.ADAQ
Body Length:
6.000 inches
MRC:
A measurement taken at right angles to the length of the body,in distinction from thickness.ADAT
Body Width:
4.125 inches
MRC:
The element,compound,or mixture of which the case is fabricated,excluding any surface treatment.ADTV
Case Material:
Plastic
MRC:
The center to center distance between terminals parallel to the length of the item.AEBP
Center To Center Distance Between Terminals Parallel To Length:
5.000 inches
MRC:
The center to center distance between terminals parallel to the width of the item.AEBQ
Center To Center Distance Between Terminals Parallel To Width:
1.375 inches
MRC:
The distance between centerlines of mounting facilities parallel to the length of the item.AEBY
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length:
4.687 inches
MRC:
The distance between centerlines of mounting facilities parallel to the width of the item.AEHA
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width:
1.375 inches
Boss Height:
0.250 inches
Mounting Surface To Terminal End Distance:
3.125 inches
MRC:
The number of poles included in the item.AKPX
Pole Quantity:
3
MRC:
Indicates the type and number of facilities by which the item is mounted.AXHR
Mounting Facility Type And Quantity:
4 slot
MRC:
The maximum current load that each pole is rated to carry continuously.CPLM
Maximum Continuous Load Current Rating Per Pole:
3.0 amperes ac all locations
MRC:
Indicates the type and value of operating voltage for which each pole is designed to operate,expressed in volts.CPRF
Operating Voltage Type And Rating Per Pole In Volts:
480.0 ac all locations
MRC:
Indicates the type and value of the maximum short circuit current that the item will successfully interrupt,per pole,at the specified rated voltage,expressed in amperes.CPRG
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps:
5000.0 ac all locations
MRC:
Indicates the type of electrical condition that will cause the device to trip.CPRH
Circuit Protection Type:
Overcurrent all locations
MRC:
The means by which the trip mechanism is released.CPRJ
Trip Release Method:
Magnetic-hydraulic all locations
MRC:
Indicates the type and voltage rating required to operate the auxiliary /remotely actuated/ trip actuator,expressed in volts.CPRK
Auxiliary Trip Coil Voltage Type And Rating In Volts:
220.0 ac all locations
MRC:
Denotes the type of trip release action.CPRL
Trip Release Characteristic:
Instantaneous all locations and time delay all locations
MRC:
The continuous current rating per pole at which the device must trip in a specified time,expressed in percent.CPRN
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
125.0 all locations
MRC:
The means provided to reposition the mechanism so that the device is ready to function.CPRQ
Reset Method:
Manual
MRC:
Indicates the type of mechanism provided for tripping main contacts.CPRR
Main Contact Tripping Mechanism Type:
Trip free
MRC:
Indicates the type and number of actuators provided for manual control.CPRT
Manual Actuator Type And Quantity:
1 toggle
MRC:
The basic internal electrical configuration of the trip mechanism.CPSM
Internal Trip Release Configuration:
Series/relay trip all locations
MRC:
The working period which the trip release is designed to operate.CQQC
Trip Release Duty Cycle:
Intermittent all locations
MRC:
The length of time,expressed in seconds,that an overload may exist before the device will trip at a specified continuous current.CQWN
Trip Delay Time In Seconds Per Rated Continuous Current:
0.150 at 200 pct all locations and 0.600 at 200 pct all locations
MRC:
The cycles per second /hertz/ of the alternating current.FREQ
Frequency In Hertz:
50.0 all locations or 60.0 all locations