رقم الجزء
تجريد
صلاحيه
UOM
NIIN
TXT
وصف:
Circuit Breaker Tripper
MRC:
The style designation indicating the configuration that most nearly corresponds to the appearance of the body.AAQL
Body Style:
Rectangular dimensional envelope
MRC:
The dimension measured along the longitudinal axis with terminated points at the extreme ends of the item.ABHP
Overall Length:
10.125 inches
MRC:
The distance measured in a straight line from the bottom to the top of an item.ABKW
Overall Height:
3.812 inches
MRC:
An overall measurement taken at right angles to the length of an item,in distinction from thickness.ABMK
Overall Width:
5.125 inches
MRC:
The length of a straight line which passes through the center of an unthreaded mounting hole,and terminates at the circumference.AEBV
Unthreaded Mounting Hole Diameter:
0.281 inches
MRC:
The number of poles included in the item.AKPX
Pole Quantity:
3
MRC:
Indicates the type and number of facilities by which the item is mounted.AXHR
Mounting Facility Type And Quantity:
4 unthreaded hole
MRC:
Indicates the type of storage space required for an item in order to provide the degree of protection necessary to maintain serviceability standards.BBRG
Storage Type:
General purpose warehouse
MRC:
The maximum current load that each pole is rated to carry continuously.CPLM
Maximum Continuous Load Current Rating Per Pole:
225.0 amperes ac all locations
MRC:
Indicates the type and value of operating voltage for which each pole is designed to operate,expressed in volts.CPRF
Operating Voltage Type And Rating Per Pole In Volts:
600.0 ac all locations
MRC:
Indicates the type of electrical condition that will cause the device to trip.CPRH
Circuit Protection Type:
Overcurrent all locations
MRC:
The means by which the trip mechanism is released.CPRJ
Trip Release Method:
Thermal-magnetic all locations
MRC:
Denotes the type of trip release action.CPRL
Trip Release Characteristic:
Time delay all locations
MRC:
The continuous current rating per pole at which the device must trip in a specified time,expressed in percent.CPRN
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
125.0 all locations
MRC:
Indicates the type and number of actuators provided for manual control.CPRT
Manual Actuator Type And Quantity:
1 toggle
MRC:
Denotes the action imparted by actuator operation.CPRW
Actuator Function:
Trip-reset
MRC:
An indication of the designated position of the actuator.CPRX
Actuator Position Designation:
At pole two
MRC:
The length of time,expressed in seconds,that an overload may exist before the device will trip at a specified continuous current.CQWN
Trip Delay Time In Seconds Per Rated Continuous Current:
250.000 at 200 pct all locations and 430.000 at 200 pct all locations
MRC:
The temperature of the medium surrounding the trip release at which it can be operated continuously.CRCF
Trip Release Ambient Tempurature Rating:
50.0 degrees celsius all locations
MRC:
The cycles per second /hertz/ of the alternating current.FREQ
Frequency In Hertz:
60.0 all locations
MRC:
Indicates the type and number of terminals for providing electrical connection.TTQY
Terminal Type And Quantity:
6 threaded stud